Numerical analysis of heat exchanger designs for passive spent fuel pool cooling to ambient air


Numerical analysis of heat exchanger designs for passive spent fuel pool cooling to ambient air

Unger, S.; Krepper, E.; Hampel, U.

Passive cooling of spent fuel pools via natural two-phase convection of a fluid with low boiling point is a promising alternative to active cooling circuits as such a passive heat transfer system would still work in safety-critical situations, such as a station blackout. For ambient air as the ultimate heat sink the heat exchanger design plays a crucial role as driving temperature differences may be low. This paper outlines a numerical investigation on a finned oval tube bundle heat exchanger operated under natural air convection in a chimney. We studied the role of chimney geometry and heat exchanger fin geometry. With respect to the chimney we found that velocity, Nusselt number and heat transfer are enhanced by 161.3%, 31.7% and 62.5% respectively, if chimney height increases from 2 m to 16 m. With respect to the fin design we determined an optimal fin configuration with a fin height of 17 mm, fin spacing of 3 mm and fin thickness of 1.5 mm, which improves the heat transfer performance by 28.7%, the Nusselt number by 28.9% and the fin efficiency by 19.2% at a given temperature difference of 40 K. The final optimized finned tube bundle heat exchanger design achieves a volumetric heat transfer density of q_vol=3.61 kW/m³K.

Keywords: passive cooling; spent fuel pool; natural convection; heat exchanger; air cooling; design optimization

Permalink: https://www.hzdr.de/publications/Publ-26410